Case Studies

Typical Office Building

AHU condenser section
AHU condenser section

Problem: What do we do with a 50-ton AHU condenser section which is hard mounted to a roof and the compression vibration is transmitting into the office below?

Solution: Cut main support at condenser side and install 3” deflection free standing spring along with safe support tube.

Robert Wood Johnson

Transformer
Transformer

Problem: The vibration from a 1500 KVA transformer (located above the operating room) causes sensitive operating room equipment and machinery to shut down…and the building is located in a seismic zone.

Solution: Cut core section away from casing and installed “free-standing” 2-inch deflection springs in combination with seismic snubbers.

Pipe Riser

Pipe riser
Pipe riser

Problem: What do we do when you are faced with pipe riser vibration and it is creating air borne noise?

Solution: Re-support with 3” deflection springs and an additional 1” vinyl loaded pipe wrap to reduce the air borne noise.